Change De-Scale Notification Interval
Like the others, this feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
Starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 possible settings:
Rev 5 and up (10/08 production start)
• 1 year (8760 hours)
• 0 (disabled)
• 4 months (2920 hrs)
• 6 months (4380 hours) (default)
Prior
• 6 months
• 5 months
• 4 months
• 3 months
3. Press Off or leave untouched for 60 seconds to select the displayed interval
Test Mode Sequence Table - Air or Water Cooled
Time (seconds) On Off
0 WIV - 30 seconds WP, HGV, Comp, Fan, PV
30 WP - 10 seconds WIV, HGV, Comp, Fan, PV
40 WP, PV, HGV - 10 seconds WIV, Comp, Fan
50 HGV, Comp - 5 seconds WIV, WP, Fan, PV
55 Comp - 15 seconds WIV, HGV, WP, Fan, PV
70 None - 5 seconds All
75 HGV - 10 seconds WIV, WP, Comp, Fan, PV
85 Fan - 10 seconds WIV, HGV, WP, Comp, PV
95 None All – Test Complete
October 2008 Page 41
Control Button Use - continued